Machine room heat pipe air conditioning
Classification:
Case description
Product Introduction
The heat pipe air conditioning system in the base station room perfectly integrates heat pipe heat exchange and active compression refrigeration technology, achieving efficient and energy-saving operation. When the heat pipe system is in operation, the cold outdoor air is introduced into the heat pipe heat exchanger through an induced draft fan for energy exchange. Then, the hot air from the machine room is introduced into the heat pipe heat exchanger through the forced draft fan for heat exchange and sent to the communication room for cooling treatment. This reduces the operating time of the compressor, prolongs its service life, saves operating and maintenance costs, and achieves the goal of energy conservation and consumption reduction. The energy efficiency ratio of air conditioning is around 3.0, and the energy efficiency ratio of heat pipe heat exchange is around 8.
When the weather is relatively hot, run the air conditioning function. When the weather is relatively cool (with a temperature difference of 6 ℃ between the inside and outside), run the heat pipe function. The intelligent controller can intelligently judge the operation of the air conditioning and heat pipe. Widely used in communication base stations, computer rooms, IDC data centers, containerized shelters, and other occasions that require heat dissipation.
The heat pipe air conditioning in the base station room relies on a single system to achieve dual working modes of air conditioning and heat pipe. Equipped with internal and external temperature sensors, the intelligent controller automatically controls the operation of the heat pipe and air conditioning, prioritizing the operation of the heat pipe to achieve maximum energy-saving effect. Widely used in communication base stations, computer rooms, IDC data centers, containerized shelters, and other occasions that require heat dissipation.
Technical Parameter
1. Lange's patented product, which shares a system between air conditioning and heat pipes, greatly enhances the reliability of the equipment.
2. The air conditioning and heat pipe share the same system, greatly improving the efficiency of the air conditioning and heat pipe.
3. The air conditioning system and heat pipe system can be intelligently switched and remotely monitored.
4. The energy-saving effect is very significant
5. Digital temperature controller with high temperature control accuracy.
6. The main components have passed CE certification and comply with EU ROHS requirements.
7. Modular machine design, which can be freely combined according to the size of the on-site space, facilitating transportation and installation.
Machine room heat pipe air conditioning split unit module machine
Model |
RGAC-6500-2 |
RGAC-8500-3 |
RGAC-12500-3 |
|
Working voltage |
220VAC±10% 50Hz |
380VAC±10%50Hz |
||
Rated power (KW) |
2.3 |
2.8 |
4.1 |
|
Refrigeration capacity (KW) |
6.9 |
9.1 |
13.2 |
|
Heat exchange capacity of heat pipe (KW) (△ T=10 ℃) |
3.2 |
4.0 |
6.5 |
|
Refrigerant |
R134A/R22 |
|||
Working temperature range (℃) |
-20~+45 |
|||
Weight (Kg) |
220 260 |
310 |
||
Colour |
RAL7035 |
|
||
IP GRADE |
|
IP23 |
|
|
External circulation air volume (m ³/ H) |
4500 |
4800 |
6300 |
|
Internal circulation air volume (m ³/ H) |
3400 |
4500 |
5200 |
|
Overall dimensions L * W * H (mm) |
Internal machine |
850×650×2000 |
850×650×2000 |
850×650×2000 |
External machine |
1025×1085×600 |
1025×1085×600 |
1065×1235×600 |
Dual compressor precision air conditioning series
Model |
SAC-11000-3 |
SAC-13000-3 |
SAC-15000-3 |
|
Working voltage (V) |
380VAC±10% 50Hz |
|||
Rated power (KW) |
3.6 |
4.3 |
5.2 |
|
Refrigeration capacity (KW) |
11.4 |
13.7 |
16.2 |
|
Heat exchange capacity of heat pipe (KW) (△ T=10C) |
5.6(option) |
6.7(option) |
7.5(option) |
|
Refrigerant |
R134A/R22 |
|||
Working temperature range (℃) |
-20~+45 |
|||
Weight (Kg) |
260 |
280 |
300 |
|
Colour |
|
RAL7035 |
|
|
IP GRADE |
|
IP23 |
|
|
External circulation air volume (m ³/ H) |
6300 |
6500 |
7200 |
|
Internal circulation air volume (m ³/ H) |
5200 |
5300 |
5500 |
|
Overall dimensions L * W * H (mm) |
Internal machine |
850×650×2000 |
850×650×2000 |
850×650×2000 |
External machine |
1065*1235*600 |
1065*1235*600 |
1170*1340*600 |