Fresh air system in the computer room
Fresh air system in the computer room
+
  • Fresh air system in the computer room
  • Fresh air system in the computer room

Fresh air system in the computer room

Classification:

Consultation:

Case description

Product Introduction

The main part of the energy-saving fresh air system in the base station room is composed of three parts: the main control box, fresh air execution system, and network management center, including the inlet fan, outlet fan, indoor and outdoor temperature sensors, automatic valves, air filters, AC transformers, outdoor rain covers, and intelligent controllers. This system introduces clean outdoor cold air based on the temperature difference between the indoor and outdoor environmental conditions of the communication base station and the computer room to naturally cool the communication base station and the computer room. At the same time, it exhausts hot air from the base station and the computer room, achieving the effect of replacing air conditioning refrigeration under most conditions throughout the year, avoiding energy waste caused by long-term operation of the air conditioning, and effectively reducing the operating time of the communication room air conditioning, To achieve the goal of reducing electrical energy consumption in communication rooms.

Product advantages

1. It adopts a microprocessor controller with a Chinese operation interface, and the system can choose manual/automatic operation mode.

2. Real time monitoring of indoor and outdoor temperature and humidity. Realize linkage with the computer room air conditioning through intelligent control.

3. The system has a delayed start function and an LCD display screen with Chinese characters display function, which is fresh and easy to operate, and can be used for parameter settings.

4. The communication interface adopts RS-485 intelligent interface to achieve telemetry, remote signaling, and remote control.

5. Low noise, good dust prevention effect, and significant energy-saving effect.

6. The intake and exhaust devices of the fresh air system have insect proof, waterproof, and anti-theft functions, without reverse flow.

7. It has fault alarm function, ultra-low temperature and ultra-high temperature alarm function.

 

Technical Parameter

model

FC-5000

FC-8000

FC-10000

FC-12000

Rated voltage (M)

220V/50HZ

Rated power (W)

1500

3000

4000

4500

Circulating air volume (m ³/ H)

5000

8000

10000

12000

Current (A)

6.8

13.6

18.2

20.5

Colour

 

RAL7035

Weight (kg

90

110

120

150

Air intake system size

long × wide × Height (mm)

650×650×1400

750×750×1550

750×750×1550

750×750×1650

Air outlet system size

long × wide × Height (mm)

500×470×350

700×640×410

770×710×435

820×810×480

 

 

Related Products

online message

Our staff will contact you within 24 hours (working days)